Specifications

Types of thermal resistors supported by converter50M, 100M, 50P, 100P, Pt50, Pt100, Pt500, Pt1000
Controlled medium measurement temperature range, ℃from -200 to +850 (is determined according to used thermal resistance)
Limit of main / additional 1) temperature measurement inaccuracy, ℃ / ℃/10℃±0.5 (±0.25 - on order) /
±0.25 (±0.1 - on order)
Климатическое исполнение по ГОСТ 15150
Ambient temperature range, ℃from -50 to +60
Water and dust ingress protection degree as per IEC 60529IP66
Explosion protection marking1Ex db IIB T4 Gb
Length of power and signal line, m, not more than length of signal line1 500
Power supply voltage (Up), Vfrom 5 to 15 (SENS line)
Intake current, mA, not more than5
Average lifetime, years15

Note.

1) Additional inaccuracy is caused by change of ambient temperature by each 10 ℃ from standard conditions (20 ℃) within operational temperature range