SENS SG-A1 gas detector
Remote measurement of under-explosive concentrations of combustible gases and vapors of petroleum products.

Specifications

Detectable componentspropane, methane, butane, hexane
Verification gasespropane, methane
Measurement range, % of LELfrom 0 to 100
Sampling method
Principle of measurementoptical absorption
Interval between verifications, months24
Indications setting time (T90), s, not more than60
Heating time, s, not more than120
Nominal power supply voltage (DC), V9
Acceptable power supply voltage (DC), Vfrom 4.5 to 30 1)
Power consumption, W, not more than2.5
Interfaces (protocols)power and signal line SENS (SENS protocol),
RS-485 (protocols SENS, Modbus RTU),
4-20 mA (HART protocol)
Signal relay featuresmaximal switchable DC/AC voltage, V30 / 42
maximal switchable current, A0.5
Number of configurable thresholds of alarm signaling5
Diameter of connectible cable without armor, mmfrom 5 to 18
Maximal cross-sectional area of connectible conductors, mm², not more than2.5
Materials contacting the environmentAlSi7 (analogue of AlSi7Mg), steel 20, steel 12Cr18Ni10Ti, steel 14Cr17Ni2, AISI 431
Climatic modification as per GOST 15150
Main absolute inaccuracy within range from 0 to 60% level measurement of LEL, % LEL, not more than±3
Main relative inaccuracy of measurement withing range from 60 to 100% LFL, %, not more than±5
Ambient temperature range, ℃from -40 to +60
Protection degree as per GOST 14254IP66
Explosion-proof marking1Ex db IIB T6 Gb
9
Overall dimensions W x H x D, mm, not more than240 × 240 × 170
Mass, kg, not more3
Service life, years15
Mean time between failures, hours, not less than15000

Note.

1) when the unit is equipped with "SENS" interface maximal power voltage is limited to 18V